Gravity Load Takedown — Multi-Column

AS/NZS 1170.0 & 1170.1 · One floor schedule, multiple columns · Cumulative G & Q with live-load area reduction
Columns

One row = one floor, top → bottom. Each column has its own tributary area per floor (A columns). Units: m, m², kPa. Tick "Reduce Q" to apply the live-load area reduction (ψa = 0.3 + 3/√A) to that floor.

FloorRoofhmA · C1A · C2G (SDL)kPaQkPaψlψsReduce Q
1
2
3
4
2,896Σ governing ULS, all columns (kN)
1,990Σ SLS, all columns (kN)
2Columns

Column C1

Governing ULS 1,447.8 kN · SLS 995.1 kN

FloorA (m²)ψaG floorQ floorΣGΣQ1.35G1.2G+1.5Q1.2G+1.5ψl·QSLS
RoofROOF40.00.774140.046.5140.046.5189.0237.7168.0140.0
L340.00.774220.092.9360.0139.4486.0641.1487.8425.0
L240.00.774220.092.9580.0232.3783.01,044.5807.5710.1
L140.00.774220.092.9800.0325.21,080.01,447.81,127.3995.1
FOOTING (C1)800.0325.21,080.01,447.81,127.3995.1

Column C2

Governing ULS 1,447.8 kN · SLS 995.1 kN

FloorA (m²)ψaG floorQ floorΣGΣQ1.35G1.2G+1.5Q1.2G+1.5ψl·QSLS
RoofROOF40.00.774140.046.5140.046.5189.0237.7168.0140.0
L340.00.774220.092.9360.0139.4486.0641.1487.8425.0
L240.00.774220.092.9580.0232.3783.01,044.5807.5710.1
L140.00.774220.092.9800.0325.21,080.01,447.81,127.3995.1
FOOTING (C2)800.0325.21,080.01,447.81,127.3995.1